HENLEY FRHF COMPOUND INSULATED ELECTRICAL WIRE |
|
Salient Features |
|
Introducing Henley FRHF Pvc Insulated Electrical Cables for working voltage upto & including 1.1 KV. These Cables are manufactured from electrolytic grade copper conductor, uniformly bunched together in circular construction and insulated with specially formulated high grade ecofriendly non toxic & corrosive, 100% Flame Retardant Halogen Free Compound with excellent electrical insulation properties. Insulation does not burn rapidly. It doesn't melt and drip to spread the fire. In the event of persistence fire, the near total absence of smoke, non-toxic and non-corrosive gases makes rescuing and fire fighting easier.
|
|
|
|
|
SPECIFICATION |
TEST |
AIM |
TYPICAL VALUES FRHF WIRES |
ASTM-D 2863 |
Oxygen Index |
To determine at room temp, the % of oxygen needed to burn the insulating material |
More than 34 % |
ASTM-D 2863 & BICC Handbook Chapter No. 6 |
Temperature Index |
To determine temp. at which 21% Oxygen in the air will burn the insulating material. |
More than 300°C |
ASTM-D 2843 |
Smoke Density |
To determine the visibility in case the Insulating Material ever catches fire. (Transmission of Light) |
More than 90% |
IEC 754-1 |
Acid Gas Generation |
To determine the amount of Hydro-Chloric, Hydro-Flouric and Halogen Acid Gases produced from burning of Insulating Material. |
Less than 5% |
|
Specification generally conform to IEC 332-1 & 3, IEEE 383, IEC 754-1 & 2, BS 4066 - 1 &3. |
CONDUCTOR NOMINAL AREA[SQ.MM.] |
NO./DIA.OF STRAND [MM.][#] |
THICKNESS OF INSULATION[NOMINAL][MM.] |
APPROX.OVERALL DIAMETER{MM} |
CURRENT CARRYING CAPACITY[*] 2 CABLES SINGLE PHASE AC OR DC.BUNCHED & CLIPPED DIRECT ENCLOSED IN TO SURFACE ORCONDUIT OR CABLE TRAY TRUNKING |
BUNCHED & ENCLOSED [AMP.] |
MAX. CONDUCTOR RESISTANCE AT 20 DEGREE COHM/KM. |
1.0 |
1/1.13 |
0.7 |
2.65 |
11 |
12 |
18.1 |
1.5 |
3/0.80 |
0.7 |
3.35 |
13 |
16 |
12.1 |
2.5 |
3/1.04 |
0.8 |
3.90 |
18 |
22 |
7.41 |
4.0 |
7/0.85 |
0.80 |
4.20 |
24 |
29 |
4.61 |
6.0 |
7/1.04 |
0.8 |
4.80 |
31 |
37 |
3.08 |
10.0 |
7/1.35 |
1.0 |
6.15 |
42 |
51 |
1.83 |
16.0 |
7/1.70 |
1.0 |
7.20 |
57 |
68 |
1.15 |
[#]:- AS PER CLASS 2 OF IS:8130:84.
INSULATION :- TYPE- A of IS:5831:84.
[*]:- CURRENT RATING AS PER IS:3961[Pt-V] : 1968.
PACKING:- IN 90 MTRS, 180 MTRS, 270 MTRS LENGTH COILS.
COLOURS:- RED, YELLOW, BLUE, BLACK, GREEN OR GREY WITH WHITE STRIPES
TYPICAL APPLICATION:-